ALARM MODULE - DC INPUT TO SINGLE ALARM

DMD1080 Series

ALARM MODULE - DC INPUT TO SINGLE ALARM  ISOLATED, FIELD CONFIGURABLE, DIN RAIL | DMD1080 Series

MXN7,970.00 DMD1080

  • Easy Field Setup --- One Minute Setup for 24 Input Ranges
  • Switch Selectable Relay Configuration
  • Removable Plugs for Faster Installation
  • Input Tracker and Alarms Status LEDs
  • Full 1200V Isolation
  • Alarm Test/Reset Button
  • Built-In Loop Power Supply for Sink/Source Input
Instrumentación para la medición de presión y tensión - Ver Productos Relacionados

Descripción

The DMD1080 accepts a DC voltage or current input and provides visual alarm indication and alarm relay contact outputs. 15 voltage and 9 current input ranges can be field configured via external rotary and slide switches. Offset ranges such as 1 to 5 Vdc and 4 to 20 mAdc are also included. Heavy-duty relay contacts allow the module to directly control high capacity loads. Front accessible potentiometers are used to adjust the alarm setpoint from 0 to 100% and the deadband from 1 to 100%. The unit provides a single setpoint adjustment of the two DPST relay contacts. The alarm output can be field configured for HI or LO operation, latching or non-latching, and normal or reverse acting.

Specifications
Input Ranges: 24 field selectable ranges via switch settings
    Voltage: 0-50 mV to 0-10 Vdc
    Bipolar Voltage: ±5 Vdc or ±10 Vdc
    Current: 0-1 mADC to 0-20 mADC, 4-20 mADC
Input Impedance and Burden:
    Voltage: 250 kΩ minimum
    Current: 50 Ω typical
    Voltage Burden: 1 Vdc at 20 mA current input
Isolation:
    1200V Isolation: power to input 600 Vac or 600 Vdc common mode protection
Input Loop Power Supply: 15 Vdc ±10%, 25 mADC maximum ripple, less then 10 mV rms may be wired for sinking or sourcing mA input
Relay Output: Single setpoint dual DPST contacts, field configurable; 2 Form A (NO) and Form B (NC) contact sets (8 terminals) may be wired for C Form operation
Relay Contact Ratings:
    8 Amps @ 240 Vac resistive load
    5 Amps @ 240 Vac inductive load
    8 Amps @ 30 Vdc resistive load
    3.5 Amps @ 30 Vdc inductive external contact protection such as a RC snubber is recommended for inductive loads
Set Point: 12 turn potentiometer adjustable from 0 to 100% of span
Deadband: 12 turn potentiometer adjustable from 1 to 100% of span
Response Time: 70 milliseconds typical
Functional Test/Reset Button: Toggles relay to opposite state when pressed; resets latching relay if latching relay mode is selected
Ambient Temperature Range and Stability:-10 to 60°C (14 to 140°F) operating ambient; better than 1% of span over operating temperature range; better than 0.02% of span per °C
Power: 60 to 265 Vac, 50/60 Hz or 85 to 300 Vdc, 2W maximum
    DC Versions: 9 to 30 Vdc or 10 to 32 Vac, 50/60 Hz, 2W maximum
Housing: Mounts to standard 35 mm DIN rail, IP40 rating
Connectors: Four 4-terminal removable connectors 14 AWG maximum wire size
Dimensions: 22.5 W x 117 H x 122 mm D (0.89 x 4.62 x 4.81")
Hacer Pedido(Especifique el Número de Modelo)
Número de parte/Desc.
Cant.
Descripción
Quick Ship
DMD1080
MXN7,970.00
Disponible en: Disponible
 
Standard power input, DC input alarm module, isolated, field configurable
Quick Ship
DMD1080-DC
MXN7,970.00
Disponible en: 5 Semanas
 
Low power input, DC input alarm module, isolated, field configurable
Todas las cantidades que se muestran en MXN
Nota: Comes complete with operator’s manual.
Ejemplo de pedido: (1) DMD1080 DC input alarm module with fully isolated alarm output, MXN7,970.00
Did you know Omega has an office in the United States with local pricing and live engineers to support you in your time zone?