En México: 01800-953-00-93
Correo de Ventas:ventas@mx.omega.com

Isolated DIN Rail Signal Conditioner

DRSL-DC2

Isolated DIN Rail Signal Conditioner | DRSL-DC2

Isolated DIN Rail Signal Conditioner

MXN6,995.00 DRSL-DC2

1 año de garantía CE
  • Isolation and Conversion of Process Voltage or Current Signals
  • Power Supply and Signal Isolator for 2-Wire Transmitter
  • Slimline Housing—Only 6 mm (0.24") Wide
  • Multiple Signal Ranges (DIP-Switch Selectable)
  • High Accuracy, <0.05% of Span
  • Fast Response Time <7 ms
Instrumentos de medición y control de proceso - Ver Productos Relacionados

Descripción

The DRSL-DC2 isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC2 can be used for signal conversion of standard process voltage or current signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

The DRSL-DC2 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. When the input is configured for 2-wire transmitter mode, the DRSL-DC2 provides the current loop supply voltage. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
INPUT
Current Input
    Measurement Range: 0 to 20.5 mA
    Functional Range: 0 to 23 mA
    Programmable Measurement Ranges: 0 to 20 mA and 4 to 20 mA
    Input Voltage Drop: <1.5V
    2-Wire Transmitter Supply: >17V/20 mA
Voltage Input
    Measurement Range: 0 to 10.25V
    Functional Range: 0 to 11.5V/ 0 to 5.75V
    Programmable Measurement Ranges: 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V
    Input Resistance: ≥500 kΩ

OUTPUT
Current Output
    Signal Range: 0 to 20.5 mA (span)
    Programmable Signal Ranges: 0 to 20 mA and 4 to 20 mA
    Load: 23 mA/600 Ω max
    Load Stability: ≤0.01% of span/100 Ω
    Current Limit: ≤28 mA
Voltage Output
    Signal Range: 0 to 10V
    Programmable Signal Ranges: 0 to 10, 2 to 10, 0 to 5 and 1 to 5V
    Load: >10 kΩ min

GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 1.2 W max
Internal Consumption: 0.4 W typical/0.65 W max
Isolation: Input/output/supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
MTBF: >231 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Span: Corresponds to the presently selected DIP switch output range
Accuracy: <±0.05% of span
Temperature Coefficient: <±0.01% of span/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity
    NAMUR NE 21, A Criterion, Burst: <±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
Hacer Pedido(Especifique el Número de Modelo)

Lo que han comprado otras personas: Cuando vea este icono, haga clic sobre él para abrir la lista de productos que otras personas han comprado al adquirir este modelo

Número de parte/Desc.
Cant.
Descripción
Haga clic para abrir la lista de productos que otras personas han comprado al adquirir este modeloDRSL-DC2
DRSL-DC2
MXN6,995.00
Disponible en: Disponible
 
Isolated DIN rail signal conditioner
Accessories
Haga clic para abrir la lista de productos que otras personas han comprado al adquirir este modeloDRSL-PWR-RAIL
DRSL-PWR-RAIL
MXN5,270.00
Disponible en: Disponible
 
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
Haga clic para abrir la lista de productos que otras personas han comprado al adquirir este modeloDRSL-PCU
DRSL-PCU
MXN3,620.00
Disponible en: Disponible
 
Power connector unit, 24 Vdc/2.5 A output to power rail
  
DRSL-MOD-STOP
MXN240.00
Disponible en: Disponible
 
Module stop (screwed onto power rail to support and hold mounted devices)
Todas las cantidades que se muestran en MXN
Ejemplo de pedido: (1) DRSL-DC2 Isolated DIN rail signal conditioner, MXN6,995.00  plus (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), MXN240.00  plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, MXN3,620.00  plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, MXN5,270.00, MXN6,995.00 + 240.00 + 3,620.00 + 5,270.00 = MXN16,125.00

Manuales de Productos:

Descarga Installation Guide for Signal Conditioners
Descarga DIN Rail Isolators and Signal Conditioners
We noticed you are from the US. Visit your local site for regional offers and live support.