Isolated DIN Rail Repeater/Splitter for Current Signals
|
Click for larger image. |
|
|
|
|
|
|
The DRSL-SP1 isolated repeater/
splitter provides a competitive
choice in terms of both price and
technology for galvanic isolation of
current signals to SCADA systems
or PLC equipment. Two current
outputs are provided which mirror
the single current input.
The DRSL-SP1 can be used for
signal conversion of a standard
process current signal into two
individual analog signals. The unit
offers 4-port isolation, provides
surge suppression and protects
control systems from transients
and noise. The DRSL-SP1 also
eliminates ground loops and can be
used for measuring floating signals.
Low power consumption facilitates
DIN rail mounting without the need
for any air gap. Measurement
ranges are factory calibrated.
The unit operates over a wide
temperature range from -25 to 70°C
(-13 to 158°F).
SPECIFICATIONS
CURRENT INPUT
Measurement Range: 0 to 20.5 mA
Functional Range: 0 to 23 mA
Input Voltage Drop: <1.5 Vdc
CURRENT OUTPUT
Number of Outputs: 2
Signal Range: 0 to 20.5 mA (span)
Load: 23 mA/300 Ω maximum
Load Stability: ≤0.01% of span/100 Ω (span = 0 to 20 mA)
Current Limit: ≤28 mA
GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 0.8 W max
Internal Consumption: 0.4 W typical/0.65 W max
Isolation: Input/output 1/ output 2/supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
Signal/Noise Ratio: > 60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Accuracy: < ±0.05% of span
Temperature Coefficient: <±0.01% of span/°C
EMC Immunity Influence: < ±0.5% of span
Extended EMC Immunity
NAMUR NE 21, A Criterion, Burst: <±1% of span
ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II
MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
|
| |
|
|
|
|
|
† All dollar amounts on this site are shown in US currency.
Ordering Example: (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), USD$240.00, plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, USD$3,625.00, plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, USD$5,275.00, plus (1) DRSL-SP1 Isolated repeater/splitter for current signals, USD$7,155.00, USD$240.00 + 3,625.00 + 5,275.00 + 7,155.00 = USD$16,295.00
|
|
|
|
|
| |
Related Links -
Manual, Related Products
|
Product Manual |
Download Installation Guide for Signal Conditioners |
Download DIN Rail Isolators and Signal Conditioners |
Related Products |
|
|
DRSL-DC2: |
Isolated DIN Rail Signal Conditioner |
|
|
|
DRSL-DC3: |
Isolated DIN Rail Signal Conditioner |
|
|
|
DRSL-DC4: |
Bipolar Isolated DIN Rail Signal Conditioner for Process Signals |
|
|
|
DRSL-SP2: |
Isolated DIN Rail Signal Conditioner/Splitter for Process Signals |
|
|
|
DRSL-SP3: |
Bipolar Isolated DIN Rail Signal Conditioner/Splitter for Process Signals |
|
|
|
|
|
|
|
DRSL-RTD-LP: |
RTD Input Non-Isolated DIN Rail Loop-Powered Signal Conditioner |
|
|
|
DRSL-TEMP: |
Isolated DIN Rail Loop-Powered Temperature Signal Conditioner |
|
|
|
DRSL-U: |
Isolated Universal Input DIN Rail Signal Conditioner |
|
|
|
|
|
|