The M12TX RTD transmitter is easily ranged and
programmable by a computer.
The configuration kit required for
programming is M12TX-CONFIG.
This unique transmitter is ideal
for areas with space limitations
where traditional head
connections are too large to fit.
The M12 thread design offers a
secure industrial connection. The
integrated connection allows the
transmitter to be mounted directly
on to the sensor.
Specifications
Body: Thermoplastic material
Connection:
M12x1 Male: In accordance to VDE0627 (output connection)
M12x1 Female: In accordance to VDE0627 (input connection Pt100)
Sensor: RTD Pt100 (alpha symbol 0.00385) 3-wire connection
Range: -50 to 500°C (-58 to 932°F)
Sensor Break Monitoring:
Selectable: Upscale (>21.0 mA) or downscale (<3.6 mA) action
Sensor Short-Circuit: Fixed to downscale (<3.6 mA) action
OutputSignal: 4 to 20 mA
Factory Scaling: 4 to 20 mA Output = 0 to 150°C Default Setting
Permissible Load: 700 @ 24Vdc [RLo= (Vsupply-8,5)/0,020]
Response Time (90%): <50 ms
Isolation In-Out: Non-isolated
Power Supply: 8.5 to 32 Vdc (polarity protected)
Environment Conditions
Temperature: -40 to 80°C (-40 to 176°F) (for plastic body)
Relative Humidity: 0 to 100%
EMC: In accordance to EN 61326
Degree of Protection: IP65 and IP67 in accordance to IEC60529
Accuracy
Transmitter: Maximum of ±0,2°C or ±0.2% of span
Sensor: Class A in accordance to IEC751
Temperature Influence [Deviation from 20°C (68°F)]: Maximum of ±0.3°C/25°C (77°F) or ±0.3% of span/25°C (77°F)
Supply Voltage Influence: Negligible
Range Configurations: It is possible set the input temperature range (span) by the M12TX-CONFIG configuration kit (PC with OS Windows® required)
Zero Adjustments: Any value between -50 to 50°C (-58 to 122°F)
Minimum Span: 50°C (122°F) [if the zero value is set between one of these values: -40°C (-40°F), -20°C (-4°F), 0°C (32°F), 20°C (68°F), 40°C (104°F), the minimum span is 20°C (68°F) rather than 50°C (122°F)]
Sensor Error Compensation: Over 2 points (maximum 1% of span)
Factory Setting: 0 to 150°C (32 to 302°F)/sensor break >21 mA (upscale)
TRANSMITTER COMPATABILITY TABLE |
Transmitter Model |
Transmitter Output |
Compatible Omega Sensors |
M12TX-PT100 | 4 to 20 mA | PR-21, PR-26, PR-31, …-2(option), PR-22, P-L-M12 |
*The M12TX-PT100 is compatible with all sensors with a "-2" European wiring option. For example: PR-26A-3-100-A-1/4-1200-M12-2, the -2 at the end of the part number specifies the wiring. The PR-22 probes have standard european wiring.
|
| |
|
|
|
|
|
† All dollar amounts on this site are shown in US currency.
Note: Comes complete with operator’s manual.
Ordering Example: (1) M12TX-PT100 RTD Temperature transmitter with M12 input connector for Pt100, output 4 to 20 mA (standard), USD$3,970.00, plus (1) PR-22-3-100-A-1/8-1200-M12 100 OHM RTD, 12 inches Long x 1/8 inch diameter, USD$2,360.00, USD$3,970.00 + 2,360.00 = USD$6,330.00
|
|
|
|
|
| |
Related Links -
Manual, Related Products
|
Product Manual |
Download M12 Series - Temperature Transmitter with 100 Ohm RTD |
Download M12TX-CONFIG - Configuration Kit for M12TX |
Related Products |
|
|
PR-21 Series: |
Vibration Resistant Platinum RTD (PT100) Sensor with M12 Connector and Mounting Thread |
|
|
|
PR-26 Metric Series: |
Vibration Resistant and Bendable RTD (Pt100) Probes with M12 Connector and Mounting Threads (Metric Sizes) |
|
|
|
PR-26 Series: |
Vibration Resistant and Bendable RTD (Pt100) Probes with M12 Connector and Mounting Threads (Fractional Sizes) |
|
|
|
PR-31: |
Bendable and Vibration Resistant RTD Probes with High Temperature Molded M12 Connector |
|
|
|
|
M12CFM RTD Series: |
M12 Cables with Field Mountable Connectors for Resistance Sensors (RTDs) |
|
|
|
|
|
|
|
|
|