M12 Stainless Steel RTD Temperature Transmitters
|
Click for larger image. |
|
|
|
|
|
|
RTD 100 Ω sensor with built-in
transmitter is programmable by
a computer. The configuration
kit required for programming is
M12TX-CONFIG. This unique
probe is ideal for areas with space
limitations where traditional head
connections are too large to fit.
The M12 thread design offers a
secure industrial connection.
Specifications
Body: Stainless steel AISI 316L
Probe Length: 13 mm (0.51") and 24 mm (0.94")
Diameter: Ø 3 mm (0.1")
Probe Type: Thermowell AISI 316L SS
Probe Minimum Bending Radius: Three-times the outer diameter [except the sensing tip which length is 30 mm (1.2")]
Connection: 1/8 NPT male thread
Sensor: RTD PT100 class A up to 300°C in accordance to IEC751
Range: -50 to 120°C (-58 to 248°F)
Tmax. Electronic: 80°C (176°F)
Sensor Break Monitoring:
Selectable: Upscale (>21.0 mA) or downscale (<3.6 mA) action
Sensor Short-Circuit: Fixed to downscale (<3.6 mA) action
Output:
Signal: 4 to 20 mA
Permissible Load: 700 @ 24 Vdc [RLo= (Vsupply-8,5)/0,020]
Default Factory Setting for 4 to 20mA output: 0 to 100°C
Response Time (90%): <50 ms
Isolation In-Out: Non-isolated
Power Supply: 8.5 to 32 Vdc (polarity protected)
Environment Conditions:
Temperature: -40 to 80°C (-40 to 176°F) for plastic body
Relative Humidity: 0 to 100%
EMC: In accordance to EN 61326
Degree of Protection: IP65 and IP67 in accordance to IEC60529
Accuracy:
Transmitter: Maximum of ±0.2°C or ±0.2% of span
Sensor: Class A in accordance to IEC751
Temperature Influence [Deviation from 20°C (68°F)]: Maximum of ±0.3°C/25°C (77°F) or ±0.3% of span/25°C (77°F)
Supply Voltage Influence: Negligible
Range Configurations: It is possible set the input temperature range (span) by the M12TX-CONFIG configuration kit (PC with OS Windows required)
Zero Adjustments: Any value between -50 to 50°C
Minimum Span: 50°C (122°F) [if the zero value is set between one of these values: -40°C (-40°F), -20°C (-4°F), 0°C (32°F), 20°C (68°F), 40°C (104°F), the minimum span is 20°C (68°F) rather than 50°C (122°F)]
Sensor Error Compensation: Over 2 points (maximum 1% of span)
Factory Setting: 0 to 100°C/sensor break >21 mA (upscale)
Response Time: Diameter 3 mm <3.5 seconds, diameter 6 mm <13 seconds (test in water to IEC751- time for reaching 63.2% of instantaneous temperature change)
|
| |
|
|
|
|
|
† All dollar amounts on this site are shown in US currency.
Note: Comes complete with operator’s manual.
Ordering Example: (1) M12TXSS-PT100-13MM-1/8NPT Temperature transmitter with M12 input connector for Pt100, output 4 to 20 mA standard, 3 mm (0.118'') diameter, 13 mm (0.51'') long, 1/8 NPT, USD$4,125.00
|
|
|
|
|
| |